OpenBuildings™ Station Designer Help

Simulation run-time control Defaults

The Defaults Manager: Simulation run-time control panel contains controls used to set simulation run-time control defaults data for use in project simulations. These defaults are used when starting new projects.

SettingDescription
Number of timesteps per hour Sets the default number of simulations per hour.
Loads convergence tolerance Sets the default loads convergence tolerance, which represents the value at which loads must agree before reaching convergence. The loads convergence tolerance value is a fraction of the total load.
Temperature convergence tolerance Sets the default temperature convergence tolerance, which represents the value at which zone temperatures must agree before reaching convergence.
Min. number of warmup days Sets the default minimum number of warm up days before OpenBuildings Energy Simulator checks for convergence. If convergence is achieved, the simulation can start. The default of 6 is typical, and is usually enough to avoid false convergences and thus to produce enough temperature and flux history to start the simulation.
Max. number of warmup days Sets the default maximum number of warm up days that can be run before reaching convergence. The default of 25 is a typical number used for this task; however, some complex buildings (with complex constructions) may require more warmup days. A notification is issued if the simulation “runs” out of days and has not yet converged. The maximum value can be increased if this occurs.
Internal convection heat transfer Heat transfer from internal surfaces is computed by considering convection and radiation separately. The default modelling methods used for convection heat transfer coefficients can be specified for new projects.
  • ASHRAE simple — Sets as the default, the ASHRAE simple modeling standard, which uses fixed values of internal convection coefficients, as defined in the ASHRAE Guide.
  • ASHRAE detailed — Sets as the default, the ASHRAE detailed modeling standard, which computes heat transfer coefficients depending on the temperature difference between the air temperature and the particular surface temperature, as detailed in ASHRAE Guide.
External convection heat transfer Heat transfer from external surfaces is computed by considering convection and radiation separately. The default modeling methods used for convection heat transfer coefficients can be specified for new projects.
  • ASHRAE simple — Sets as the default, the ASHRAE simple modeling standard, which uses fixed values of external convection coefficients, as defined in the ASHRAE Guide.
  • ASHRAE detailed — Sets as the default, the ASHRAE detailed modeling standard, which computes external heat transfer coefficients based on wind speed as defined in the ASHRAE Guide.
Infiltration model For room infiltration, two models are available, a simple air change rate and a multi-zone air flow model.
  • Simple — Sets the simple model as the default for new projects, which enables you to simply define an air change rate for each room and this simple air change rate is used in design and energy calculations.
  • Multi-zone air flow — Sets the multi-zone air flow model as the default for new projects, which computes the air flow into, out of and between rooms by analyzing air movement through cracks, joints, trickle ventilators, open windows and doors, roof ventilators and many other flowpaths between rooms. In order to use the multi-zone air flow model, you must have set up air flow paths for each room.
Shadow calculation frequency Sets the default time intervals for shadow calculations to occur per design day.
Max figures in shadow overlap calculations Sets a default upper limit on the number of overlapping shadows on a single surface allowed on shadow calculations.
Heat balance algorithm Sets the default type of heat and moisture transfer algorithm used across the building construction calculations. The drop-down list contains these algorithms:
  • CoductionTransferFunction — Sets CoductionTransferFunction as the default algorithm. CTF is used to calculate conduction heat transfer in building cooling/heating loads and energy calculations.
  • MoisturePenetrationDepthConductionTransferFunction — Sets MoisturePenetrationDepthConductionTransferFunction as the default algorithm. MoisturePenetrationDepthConductionTransferFunction is a sensible heat diffusion and an inside surface moisture storage algorithm that needs additional moisture material property information.
  • ConductionFiniteDifference *1 Very slow — Sets ConductionFiniteDifference *1 Very slow as the default algorithm. ConductionFiniteDifference *1 Very slow is a sensible heat only solution that does not account for moisture storage or diffusion.
  • CombinedHeatAndMoistureFiniteElement *2 Very very slow — Sets CombinedHeatAndMoistureFiniteElement *2 Very very slow as the default algorithm. CombinedHeatAndMoistureFiniteElement *2 Very very slow is a coupled heat and moisture transfer and storage algorithm that uses finite differences in constructions and requires further material properties.
Heating Sizing Factor Sets a default global heating sizing ratio that is applied to all of the zone design heating loads and air flow rates.
Cooling Sizing Factor Sets a default global cooling sizing ratio that is applied to all of the zone design cooling loads and air flow rates.
Timesteps in averaging window Sets the default number of load timesteps in the zone design flow sequence averaging window. The default is 1, in which case the calculated zone design flow rates are averaged over the load timestep.
Inside temperature Sets the default inside temperature for the building as a whole, which is used for dew point calculations.
Ground temperature: January - December Ground floors are assumed to be in contact with the earth, for which default temperatures can be set for each month of the year.
Consider shading from recesses When on by default, recesses around windows that can partially shade the glazing are considered for simulation.
Consider shading from fins When on by default, fins defined for each window are included in the shading calculations.
Consider shading from external buildings When on by default, buildings set up as part of the shading calculation are considered.
Consider external reflections When on by default, the reflections from external buildings are considered.
Consider full internal sun distribution When on by default, heat energy transmitted into the building that is uniformly distributed to all internal surfaces apart from the ceiling is considered.
Tip: Units Display – Units are displayed using the default system of units that was defined for the project, but can be changed to display using alternative units.